Instructions

Detaileddescriptionsoftheeld-buscoupler | Probus DP eld-bus coupler UR20-FBC-PB-DP
41Manual u-remote1432790000/03/02.2014
OverviewofeditableparametersUR20-FBC-PB-DP
Parameter Additional explanations Optional values Default value
DP-Alarm mode V0 / V1 V1
DP alarm mode V0 For mode V0, the alarm triggers are set in the parameter data.
Diagnostic alarm These switches are always selectable, but they only
have a function in mode V0. Diagnostic messages are
generated which are not acknowledged by the PLC.
enabled / disabled disabled
Process alarm enabled / disabled disabled
Hot-plug alarm enabled / disabled enabled
DP alarm mode V1 In mode V1, the alarm triggers are set in the engineering environment.
Diagnostic alarm
These switches can be selected only in mode V1, in V0
they are inactive. Diagnostic messages are generated
which are acknowledged by the PLC.
enabled / disabled disabled
Process alarm enabled / disabled disabled
Hot-plug alarm enabled / disabled enabled
Identier-related diagnosis A diagnostic block is attached to the diagnostic message. enabled / disabled enabled
Channel-related diagnosis A diagnostic block is attached to the diagnostic message. enabled / disabled enabled
Module status A diagnostic block is attached to the diagnostic message. enabled / disabled enabled
Data format Motorola / Intel Motorola
Field-bus error output behaviour All outputs off / activate replacement values /
retain last value
All outputs off
Module behaviour during hot
swap
Continue data exchange /
behaviour as with eld-bus error
Continue data exchange