Detailbeschreibungen I/O-Module | Analoges Eingangsmodul UR20-4AI-RTD-DIAG
202 1432780000/03/02.2014Handbuch u-remote
Diagnosedaten UR20-4AI-RTD-DIAG
Name Byte Bit Beschreibung Default
Fehlerindikator 0
0 Module error
1 Internal error
2 External error
3 Channel error
4 Reserved 0
5 Power supply fault
6 Reserved 0
7 Parameter error
Modultype 1
0
Module type 0x05
1
2
3
4 Channel information available 1
5 Reserved 0
6 Reserved 0
7 Reserved 0
Fehlerbyte 2 2 0 ... 7 Reserved 0
Fehlerbyte 3 3
0 ... 2 Reserved 0
3 Internal diagnostic FIFO full
4 Power supply fault
5 Reserved 0
6 Process alarm lost
7 Reserved 0
Kanaltyp 4
0 ... 6 Channel type 0x71
7 Reserved 0
Diagnosenbits
pro Kanal
5
Number of diagnostic bit per
channel
8
Anzahl Kanäle 6
Number of similar channels per
module
4
Kanalfehler 7
0 Error at channel 0
1 Error at channel 1
2 Error at channel 2
3 Error at channel 3
4 ... 7 Reserved 0
Kanalfehler 8 8 ... 15 Reserved 0
Kanalfehler 9 16 ... 23 Reserved 0
Kanalfehler 10 24 ... 31 Reserved 0
Fehler Kanal 0 11
0 Parameter error
1 Reserved 0
2 Reserved 0
3 Reserved 0
4 Line break
5 Process alarm lost
6 Lower limit exceeded
7 Upper limit exceeded
Diagnosedaten UR20-4AI-RTD-DIAG
Name Byte Bit Beschreibung Default
Fehler Kanal 1 12
0 Parameter error
1 Reserved 0
2 Reserved 0
3 Reserved 0
4 Line break
5 Process alarm lost
6 Lower limit exceeded
7 Upper limit exceeded
Fehler Kanal 2 13
0 Parameter error
1 Reserved 0
2 Reserved 0
3 Reserved 0
4 Line break
5 Process alarm lost
6 Lower limit exceeded
7 Upper limit exceeded
Fehler Kanal 3 14
0 Parameter error
1 Reserved 0
2 Reserved 0
3 Reserved 0
4 Line break
5 Process alarm lost
6 Lower limit exceeded
7 Upper limit exceeded
Fehler Kanal 4
...
Fehler Kanal 31
15 ... 42 0 ... 7 Reserved 0
Zeitstempel 43-46 time stamp [µs] (32bit)