Datasheet

Data sheet
ACT20P
ACT20P-PRO DCDC II-P
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date January 24, 2020 3:25:14 PM CET
Catalogue status 13.01.2020 / We reserve the right to make technical changes. 2
Dimensions and weights
Width 12.5 mm
Width (inches) 0.492 inch
Height 127.1 mm
Height (inches) 5.004 inch
Depth 113.7 mm
Depth (inches) 4.476 inch
Weight 130 g
Net weight 20 g
Environmental Product Compliance
REACH SVHC Lead 7439-92-1
Input
Number of inputs
1
Input signal Voltage source, Current
source
Input voltage configurable, ±40 mV…
±300 V, Measuring range.
min 40 mV
Input resistance, voltage
approx. 1 MΩ
Input current configurable, ± 0.1mA...±
100 mA, Measuring range
min. 200 µA
Input resistance, current
< 5 mA: approx. 100 Ω; >5
mA: approx. 5 Ω
Output
Output voltage, note Adjustable, 0...±10 V
Output current Adjustable, 0...±20 mA
Cut-off frequency (-3 dB) > 10 kHz/ < 10 Hz
load impedance voltage ≥ 1 kΩ
load impedance current ≤ 600 Ω
Offset voltage < 10 mV
Offset current 20 µA
Status indicator Green LED
Display
Type Dot-matrix display with
ticker text, green
Display value current measured value,
Configuration data
General data
Accuracy < 0.05 % of measuring
range
Configuration DIP switch, or via display
and push-buttons
Galvanic isolation 3-way isolator, between
input ⁄ output ⁄ supply
Power consumption
≤2.3 W
Rail TS 35
Step response time ≤50 µs
Temperature coefficient
≤0.01% of the output
measurement range ⁄ °C
Voltage supply 24…230 V DC ±20 %,
24…230 V AC ±10 % @
48…62 Hz
Insulation coordination
EMC standards EN 60079-0, EN
60079-15, EN 61010-1,
EN 61140, EN 61326-1,
UL 61010-1, SN29500 for
MTBF
Galvanic isolation
3-way isolator, between
input ⁄ output ⁄ supply
Impulse withstand voltage
5 kV (1.2/50 µs)
Insulation voltage 4 kV
eff
, input ⁄ output ⁄
power supply
Pollution severity 2
Rated voltage
600 V
Surge voltage category II