User Guide

CGa, CGi, EG, EGH, LGB, PEG, Boilers
6
Part Number 550-142-801/1112
Maintain boiler using schedule below
Tankless water heater (EG and EGH only)
If boiler is used to supply domestic hot water, limit
control should be set to supply adequate hot water.
Weil-McLain tankless heaters are rated at 200 °F boiler
water temperature. To get rated output, set low limit at
200 °F. Limit can be adjusted to meet system hot water
requirements. Differential can be set to 15 ° and adjusted
to control level. Lowering the differential will cause a
slight variation in water temperature but will decrease
burner on-off cycling. High limit should be set at least
20 ° above low limit.
Service technician
(covered in Boiler Manual – for use only by a
qualified service technician)
Owner maintenance
(see following pages for instructions)
A
nnuAl
stArt
-
up
Inspect:
Reported problems
Boiler area
Air openings
Flue gas vent system
Pilot and main burner flames
Water piping
Boiler heating surfaces
Burners, base and inlet air box
Condensate drain system
Service:
Oiled-bearing circulators
Temperature sensor
Start-up:
Perform start-up per manual
Check/test:
Gas piping
Cold fill and operating pressures
Air vents and air elimination
Limit controls and cutoffs
Expansion tank
Boiler relief valve
Review:
Review with owner
Daily
Check boiler area
Check air openings
Check boiler pressure/
temperature gauge
Monthly
Check boiler interior piping
Check venting system
Check air vents
Check boiler relief valve
Check automatic air vents (if
used)
Periodically
Test low water cutoff (if used)
Every 6 months
Operate relief valve
End of season
Shut down procedure