SlimFit Suggested Specifications

Weil-McLain | 999 McClintock Drive, Suite 200, Burr Ridge, IL 60527 | Tel 630.560.3700 | www.weil-mclain.com
I. General Requirements
A. Furnish and install ________ (qty.) packaged, modulating, sealed combustion, power-vented, high efficiency gas-fired
boiler(s) with cast aluminum sectional heat exchangers that use outside or inside air for combustion.
B. Install packaged boiler unit(s) according to manufacturer’s installation instructions. All work to be done in a neat and
workmanlike manner.
C. ________ (quantity) Weil-McLain SlimFit -________ (size), ___ (L or R) packaged boiler(s) capable of burning natural
gas.
D. Boiler(s) shall have an AHRI gross output at 100% fire rate of _________ MBH per boiler.
E. Boiler(s) shall be 95+% minimum AHRI certified thermal efficient as required by BTS 2000
F. Boiler shall be capable of full modulation firing with a turn down of up to 6 to 1
G. Boiler(s) shall be manufactured by ISO 9001 registered company to conform to Section IV of the ASME Boiler and
Pressure Vessel Code
1. Sectional cast aluminum block to be fire tested and hydrostatically pressure tested at factory in accordance with
ASME requirements
2. Maximum allowable working pressure 100 PSIG water as listed on the rating label
3. Boiler(s) and controls to comply with applicable regulations
4. Boiler(s) shall be fully factory packaged in acceptance with ASME CSD-1
II. Product
A. Acceptable boiler manufacturer(s) include(s)
1. As specified in Part I, Paragraph C
2. Other manufacturer or other Weil-McLain boiler(s) must comply with specifying engineer’s requirements,
including:
(a) Full intent of these specifications
(b) Provide complete submittal including literature, manuals, wiring diagrams, fuel piping diagrams, and a list
of similar installations. Any alternate must be of similar size and footprint, piping configuration, clearance
requirements and heating surface
(c) Submittal presented to engineer at least seven working days before bid opening for approval. Substitutions
are not permitted after contract is awarded
B. Boiler Construction
1. Boiler(s) heat exchanger:
(a) Cast aluminum sectional block
2. Factory Assembled and Tested
3. Boiler(s) main components:
(a) The boiler shall have the ability to be assembled in both a left-handed and right-handed orientation. In
multiple boiler systems, this will allow two boilers, one right-handed and one left-handed, to be installed
side-by-side. This orientation will allow easy access for cleaning and maintenance, as well as placing all
gas and water connections for the two boilers directly next to one another
(b) The combustion chamber will be sealed and located at the top of the block casting which will be of counter
flow design
(c) The burner shall be premix combustion type, made with stainless steel and a woven metal fiber outer
covering to provide a wide range of modulating firing rates
SlimFit™ High Efficiency Gas Boiler