Operating instructions

Part number 550-141-887/0800
33
AHE Series 4 Direct Vent Wall-Mounted Boilers — Boiler Manual
Make sure boiler water temperature must be 100 °F or
cooler before starting procedure to obtain appropriate
readings.
Check pressure switch setting
1. Remove both air pressure switch hoses from air pressure switch.
2. Install tees and tubing as shown in Figure 27 to inclined manometer.
3. Close the manual main gas valve and set thermostat to call for heat.
Blower will run but main burners will not ignite.
4. Check for 24 VAC between normally open terminal on pressure switch
and ground. See Figure 28.
Troubleshooting air pressure reading
1. If manometer reading is at least 0.55" w.c. pressure, but there is not 24
VAC across normally open terminal on pressure switch and ground,
replace the pressure switch.
2. If manometer reading is lower than 0.55" w.c., look for possible causes:
blockage in hoses
obstruction in blower housing outlet
loose blower wheel on motor shaft
blower back plate not sealed properly
blockage in exhaust, air intake pipe or termination.
Return to normal operation
When pressure reading is correct and air pressure switch is operating
properly, remove tees and reinstall tubing to air pressure switch.
Troubleshooting — air pressure switch
12b
Figure 27 Manometer connections Figure 28 Air pressure switch
Red
Red
Pressure switch
Normally
open
Normally
closed
Common
88717
88722
Inclined tube manometer
Blower assembly
to inlet side
To burner
access cover
Suction
Pressure