AHE Series 4 Direct Vent Wall-Mounted Boilers — Boiler Manual
Troubleshooting — charts
continued
12d
CHART 5 FLAME & POWER lights flashing
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
Boiler should now operate normally.
Original flashing FLAME light caused by igniter not
operating properly.
See normal sequence of operation, Figure 17, page 22.
Open manual gas valve.
Restart boiler, following Operating instructions for gas
valve installed on boiler (pages 24 or 25).
Check for proper operation (per Sequence of operation,
Figure 17, page 22).
Boiler should now operate normally.
Original flashing FLAME light caused by gas valve not
operating properly.
See normal sequence of operation, Figure 17, page 22.
Call your local Weil-McLain
sales representative.
Check and/or replace gas valve.
Recycle boiler by thermostat or service switch.
Thermostat should call for heat and appropriate zone
valves close.
Wait 5 minutes.
Are FLAME & POWER lights flashing?
No Yes
Check and/or replace igniter.
Recycle boiler by thermostat or service switch.
Thermostat should call for heat and appropriate zone
valves close.
Wait 5 minutes.
Are FLAME & POWER lights flashing?
No Yes
Check gas valve harness wires and check for tight wiring
connections on gas valve and control module. Repair/
replace as necessary.
Recycle boiler by thermostat or service switch (holding
power off for at least 45 seconds).
Thermostat should call for heat and appropriate zone
valves close.
During step 5 of sequence of operation (Figure 17, page
22), is there 24 VAC across gas valve terminals?
No Yes
Are manual main shutoff valve and gas valve turned on?
No Yes
Replace control module.
Retest.