AHE Series 4 Direct Vent Wall-Mounted Boilers — Boiler Manual
Troubleshooting — charts
continued
12d
Remove CIRCULATOR plug (
Figure 29, page 34, Item 4
)
from plug receptacle of control module.
Place voltmeter leads across the 120 VAC N and
120 VAC H pins of the CIRCULATOR receptacle on the
side corresponding to the circulator not operating.
Does the voltmeter indicate 120 VAC?
CHART 6TSTAT CIRC light flashing and POWER light on steady
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow
instructions could result in severe personl injury, death or substantial property damage.
No Yes
Replace control module.
Retest.
Test wire continuity of
circulator wire harness.
Is harness ok?
No Yes
Replace circulator
harness.
Retest.
Reconnect circulator harness to control module.
Attempt to get the circulator started by giving it a sharp rap
on the end of the circulator motor (to release a possibly
locked impeller).
If the circulator begins to operate, allow it to operate for a
few minutes to see if the problem clears.
If problem persists, replace the circulator.
Retest.
No Yes
Is there a call for heat?
(Verify by removing thermostat wirings at boiler and checking
continuity across external wires)
This is normal operation for
water less than 40 ˚F at
boiler internal return pipe.
Condition should change
after a call for heat, when
the boiler will heat up the
water.
Wait 10 minutes to allow
heat from the boiler to
raise the water
temperature.
Does LIMIT light quit
flashing (and pipes begin to
heat up)?
No Yes
Boiler is not heating.
Troubleshoot boiler using CHART 8.
Boiler should now operate normally.
Verify correct sequence of operation using Figure 17, page
22.
No Yes
Is boiler internal circulator operating?
CHART 7LIMIT light flashing and POWER light on steady
This is not a lockout mode. The control module should only be signaling that the 47K resistor is shorted out.
This situation is usually corrected by replacing the resistor, as described below.
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow
instructions could result in severe personl injury, death or substantial property damage.
Remove RESISTOR plug from receptacle on the control module (
Figure 29, page 34, Item 6
). Then re-insert.
Does LIMIT light still flash?
No Yes
No Yes
Boiler may now be operating correctly. Verify per
normal sequnce of operation in Figure 17, page 22.
Replace 47K resistor.
Does LIMIT light still flash?
Replace control module.
Retest.