3.9 Operating structure
After supply voltage switch-on, the controller starts with the operating levels.
The controller status is as before power off.
g
PArA - level: At PArA - level, the right decimal point of the upper
display line is lit continuously.
g
ConF - level: At ConF - level, the right decimal point of upper
display line blinks.
When safety switch Loc is open, only the levels enabled by means of Blue-
Control
®
(engineering tool) are visible and accessible by entry of the pass-
word adjusted by means of BlueControl (engineering tool). Individual
parameters accessible without password must be copied to the extended ope-
rating level via BlueControl
®
.
g
All levels disabled via password are disabled only, if safety switch loc also is
open
Factory setting:
Safety switch Loc closed:
-all levels accessible without restriction,
-password PASS = OFF.
Safety switch
Loc
Password entered
with BluePort®
Function disabled or
enabled with BluePort®
Access via the instrument
front panel:
closed OFF / password disabled / enabled
enabled
open OFF / password disabled
disabled
open OFF enabled
enabled
open Password enabled
enabled after password entry
Operation
KS50/52-1 27 Operating structure