Manual

Name Value range Description Default
fAI1
Forcing INP1 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
InP.2
Name Value range Description Default
I.Fnc
Function selection of INP2
1
0
no function (subsequent input data are skipped)
1
heating current input
2
external set-point (SP.E)
5
default correcting variable Y.E (switchover -> LOGI/ Y.E)
S.tYP
Sensor type selection
31
30
0...20mA / 4...20mA
Scaling is required. (see chp. 5.3 page 51)
31
0...50mA AC
Scaling is required. (see chp.5.3 page51)
fAI2
Forcing INP2 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
Lim
Name Value range Description Default
Fnc.1
Fnc.2
Fnc.3
Function of limit 1/2/3
1
0
switched off
1
measured value monitoring
2
Measured value monitoring + alarm status storage. A stored
limit value can be reset via error list,
è-key, Ò-key or a
digital input ( -> LOGI/ Err.r)
Src.1
Src.2
Src.3
Source of Limit 1/2/3
1
0
process value
1
control deviation xw (process value - set-point)
2
control deviation xw (with suppression after start-up and
set-point change)
6
effective setpoint Weff
7
correcting variable y (controller output)
8
control variable deviation xw (actual value - internal
setpoint) = deviation alarm to internal setpoint
11
Control deviation Xw (=relative alarm) with suppression
after start-up or set-point change without time limit.
HC.AL
Alarm heat current function (INP2)
0
0
switched off
1
Overload short circuit monitoring
2
Break and short circuit monitoring
LP.AL
Monitoring of control loop interruption for heating
0
0
switched off / inactive
1
active
If ti1=0 LOOP alarm is inactive!
Configuration level
KS50/52-1 31 Configurations