Manual

Name Value range Description Default
5
transmitter supply (only visible without OPTION)
O.Act
Method of operation of output OUT3 (only visible when O.TYP=0)
1
0
direct / normally open
1
inverse / normally closed
Y.1
Y.2
Controller output Y1/Y2 (only visible when O.TYP=0)
0
0
not active
1
active
Lim.1
Lim.2
Lim.3
Limit 1/2/3 signal (only visible when O.TYP=0)
1
0
not active
1
active
LP.AL
Interruption alarm signal (LOOP) (only visible when O.TYP=0)
0
0
not active
1
active
HC.AL
Heating current alarm signal (only visible when O.TYP=0)
0
0
not active
1
active
HC.SC
Solid state relay (SSR) short circuit signal (only visible when
O.TYP=0)
0
0
not active
1
active
P.End
Programmer end signal (only visible when O.TYP=0)
0
0
not active
1
active
FAi.1
FAi.2
INP1/ INP2 error (only visible when O.TYP=0)
1
0
not active
1
active
Out.0
-1999...9999
Scaling of the analog output for 0% (0/4mA or 0/2V, only visible
when O.TYP=1..5)
0
Out.1
-1999...9999
Scaling of the analog output for 100% (20mA or 10V, only
visible when O.TYP=1..5)
100
O.Src
Signal source of the analog output OUT3 (only visible when O.TYP=1..5)
1
0
not used
1
controller output y1 (continuous)
2
controller output y2 (continuous)
3
process value
4
effective set-point Weff
5
control deviation xw (process value - set-point)
6
No function
fOut
Forcing OUT3 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
Out.5/ Out.6
Configuration parameters Out.5 as Out.1 except for: Default Y.1 =0, Y.2 =0
g
Method of operation and usage of output Out.1 to Out.6:
Is more than one signal chosen active as source, those signals are OR-linked.
Configuration level
KS50/52-1 33 Configurations