Manual

othr
Name Value range Description Default
bAud
Baudrate of the interface (only visible with OPTION)
2
0
2400 Baud
1
4800 Baud
2
9600 Baud
3
19200 Baud
Addr
1...247
Address on the interace (only visible with OPTION)
1
PrtY
Data parity on the interface (only visible with OPTION)
1
0
no parity (2 stop bits)
1
even parity
2
odd parity
dELY
0...200
Delay of response signal [ms] (only visible with OPTION)
0
Unit
Unit
1
0
without unit
1
°C
2
°F
dP
Decimal point (max. number of digits behind the decimal point)
0
0
no digit behind the decimal point
1
1 digit behind the decimal point
2
2 digits behind the decimal point
3
3 digits behind the decimal point
LED
Function allocation of the status LEDs1/2/3
0
0
OUT1, OUT2, OUT3
1
Heating, Alarm 2, Alarm 3
2
Heating, Cooling, Alarm 3
C.dEl
0..200
Modem delay [ms]
0
FrEq
Switching 50 Hz / 60 Hz (only visible with BlueControl!)
0
0
50 Hz
1
60 Hz
MASt
Modbus Master / Slave (only visible with BlueControl
®
!)
0
0
No
1
Yes
Cycl
0 ... 240 Mastercycle (sec.) (only visible with BlueControl
®
!)
120
Adr0
-32768 ... 32767 Destination address (only visible with BlueControl
®
!)
1100
AdrU
-32768 ... 32767 Source address (only visible with BlueControl
®
!)
1100
Numb
0 ... 100 Number of data (only visible with BlueControl
®
!)
1
ICof
Block controller off (only visible with BlueControl!)
0
0
Released
1
Blocked
Configuration level
Configurations 36 KS50/52-1