Manual

PAr.2
Name Value range Description Default
Pb12
1...9999 1
Proportional band 1 (heating) in phys. dimensions (
e.g. °C), 2. parameter set
100
Pb22
1...9999 1
Proportional band 2 (cooling) in phys. Dimensions
(e.g. °C), 2. parameter set
100
Ti22
0...9999
Integral action time 2 (cooling) [s], 2. parameter set
180
Ti12
0...9999
Integral action time 1 (heating) [s], 2. parameter set
180
Td12
0...9999
Derivative action time 1 (heating) [s], 2. parameter set
180
Td22
0...9999
Derivative action time 2 (cooling) [s], 2. parameter set
180
SEtP
Name Value range Description Default
SP.LO
-1999...9999
Set-point limit low for Weff
0
SP.Hi
-1999...9999
Set-point limit high for Weff
900
SP.2
-1999...9999
Set-point 2.
0
r.SP
0...9999
Set-point gradient [/min]
OFF
SP.bo
-1999...9999
Boost set-point
30
t.bo
0...9999
Boost time
10
Y.St
-120...120
Start-up setpoint (see page 56)
20
SP.St
-1999...9999
Set-point for start-up
95
t.St
0...9999
Start-up hold time (see page 56)
10
SP
-1999...9999
Set-point (only visible with BlueControl!)
0
g
SP.Lo and SP.hi should be between the limits of rnGH and rnGL see
configuration r controller page 29
ProG
Name Value range Description Default
SP.01
-1999...9999
Segment end set-point 1
100 1
Pt.01
0...9999
Segment time 1 [min]
10 2
SP.02
-1999...9999
Segment end set-point 2
100 1
Pt.02
0...9999
Segment time 2 [min]
10 2
SP.03
-1999...9999
Segment end set-point 3
200 1
Pt.03
0...9999
Segment time 3 [min]
10 2
SP.04
-1999...9999
Segment end set-point 4
200 1
Pt.04
0...9999
Segment time 4 [min]
10 2
1 If SP.01 SP.04 = OFF then following parameters are not shown
2 If segment end set-point = OFF then the segment time is not visible
Parameter setting level
KS50/52-1 49 Parameters