Manual

InH.1: The input value of the upper scaling point is displayed. .
The operator must adjust the upper input value by means of the
process value simulator and confirm the input value by pressing key Ù.
OuH.1: The display value of the upper scaling point is displayed.
Before calibration OuH.1 is equal to InH.1.
The operator can correct the upper display value by pressing keys ÈÌ
Subsequently, he confirms the display value by pressing key Ù.
2-point correction
( ConF/ InP.1 / Corr = 2 ):
is possible off-line with process value simulator
g
The parameters (OuL.1,
OuH.1) altered at CAL level
can be reset by decreasing them
below the lowest adjustment
value (OFF) using the
decrement key Ì .
Calibration level
54 KS50/52-1
X
standard setting
2-point correction
InL.1
InH.1
OuL.1
new
OuH.1new
display
OuH.1old
OuL.1old