Operation Manual

22
CAUTION:
1. Use an individual power circuit specifically for the air conditioner. As for the wiring method, refer to the
circuit diagram on the inside of the access door .
2. Check that the cable thickness conforms to the power source specification.
3. Check the wires and make sure that they are all tightly fastened after cable connection.
4. Be sure to install an earth leakage circuit breaker in a wet or moist area.
Cable Specifications
WIRING DIAGRAM
Capacity
(Btu/h)
Power cord Power connecting cord Power connecting cord 1
Main
power
supply
(Note)
Ty p e
Normal cross -
sectional area
Ty p e
Normal cross -
sectional area
Ty p e
Normal cross -
sectional area
7K,9K,12K H05VV-F 1.0~1.5mm² X3 H07RN-F 1.0~1.5mm²X3 H05RN-F
0.75mm²X2
(Heat-pump)
To indoor
18K
H05VV-F
RVV
1.5~2.0mm² X3 H07RN-F 1.5mm²X3 H05RN-F
0.75mm²X2
(Heat-pump)
To indoor
24K H07RN-F 2.5mm² X3 H07RN-F
1.5mm²X3(Heat-pump)
1.5mm²X4(Cooling-only)
H05RN-F
0.75mm²X3
(Heat-pump)
To outdoor
Make sure that the colour of wires of the outdoor unit and the terminal number are the same as those of
the indoor unit.
Power supply from Indoor unit, including 7K,9K,12K, Model
AC L-IN
AC N-IN
1(N)
2(L)
1(N)
3(SI)
2(L)
3(SI)
HEAT PUMP
Power connecting cord
Indoor unit
Te r m i n a l
Outdoor unit
Te r m i n a l
Yellow/Green
Blue (Gray)
Brown
Black
Yellow/Green
Blue (Gray)
Brown
Black
Evaporator
Indoor unit control board
Power supply
YE/GN
BN
BU