THERMOSTAT WIRING DIAGRAM
FUSEDDISCONNECT
OR CIRCUITBREAKER
:.i-'.i
g Nj
ELECTRONIC
THERMOSTAT(ET)
® ®
B---
@ a--
BLUE
UPPER_
ELEMENT"_,.#t..1
TEMPERATURE
SENSOR
o_
p,n
BLUE _ i
\ I J LOWER
BLACK _ ELEMENT
I ENERGYSMART k
MODULE(ESM)
d_l
i
-- ELECTRICAL
SERVICE
GROUND GROUND
SCREW
319165-000G
BRANCH CIRCUIT SIZING GUIDE
Based on N.E.C. NFPA NO. 70 - 1999
WATT
LOAD
1500"
2000
2500
3000
3500
4000
4500
5000
5500
Recommend
Over Current
Protection Rating
120 208 240
V V V
15 15 15
20 15 15
30 15 15
30 20 15
20 20
25 20
30 25
30 30
30
Copper Wire Size
AWG Based on
N.E.C.
Table310- 16 (60°C)
120 208 240
V V V
12 14 14
10 14 14
10 14 14
8 12 12
10 12
10 10
10 10
10 10
10
Wattages less than 1500 may be wired 14 gage with a maximum
15 amp protection.
23