Specification

571210-CTG-C-1012
Johnson Controls Unitary Products 33
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Continued on next page.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. THJD48S41S4
INDOOR COIL MODEL NO. AHP48
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1510 1710 1910
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 47.6 50.1 49.8 54.1 60.7 49.4 50.8 51.0 55.8 61.9 51.2 51.5 52.2 57.5 63.1
S.C. 47.6 44.7 37.8 37.0 30.4 49.4 48.3 39.9 39.3 31.5 51.2 51.5 42.0 41.6 32.6
KW 2.90 2.90 2.90 3.00 3.00 3.00 3.00 3.00 3.00 3.10 3.10 3.10 3.10 3.10 3.20
75
T.C. 45.1 46.6 46.5 50.8 56.9 46.7 47.2 47.5 52.2 58.0 48.4 47.9 48.5 53.6 59.0
S.C. 45.1 43.1 36.2 35.6 28.9 46.7 45.8 38.3 37.8 30.0 48.4 47.9 40.3 40.0 31.1
KW 3.20 3.20 3.20 3.20 3.30 3.20 3.20 3.20 3.30 3.30 3.30 3.30 3.30 3.40 3.40
85
T.C. 42.5 43.1 43.2 47.5 53.2 44.1 43.7 44.0 48.6 54.1 45.6 44.3 44.7 49.7 55.0
S.C. 42.5 41.5 34.7 34.2 27.3 44.1 43.3 36.7 36.2 28.4 45.6 44.3 38.7 38.3 29.6
KW 3.40 3.40 3.40 3.50 3.50 3.50 3.50 3.50 3.50 3.60 3.60 3.60 3.60 3.60 3.70
95
T.C. 40.0 39.6 39.9 44.2 49.4 41.4 40.2 40.4 45.0 50.2 42.8 40.7 41.0 45.8 51.0
S.C. 40.0 39.6 33.1 32.7 25.8 41.4 40.2 35.0 34.7 26.9 42.8 40.7 37.0 36.6 28.0
KW 3.60 3.60 3.60 3.70 3.80 3.70 3.70 3.70 3.80 3.90 3.80 3.80 3.80 3.90 4.00
105
T.C. 37.2 37.1 36.3 40.6 45.3 38.5 37.8 36.8 41.1 45.9 39.7 38.6 37.2 41.7 46.6
S.C. 37.2 37.1 31.6 31.3 24.2 38.5 37.8 33.5 33.2 25.2 39.7 38.6 35.4 35.1 26.3
KW 3.90 3.90 3.90 4.00 4.10 4.00 4.00 3.90 4.00 4.20 4.10 4.10 4.00 4.10 4.20
115
T.C. 34.5 34.5 32.8 36.9 41.1 35.5 35.5 33.1 37.2 41.6 36.6 36.4 33.5 37.6 42.1
S.C. 34.5 34.5 30.0 29.8 22.5 35.5 35.5 31.9 31.7 23.6 36.6 36.4 33.5 33.5 24.6
KW 4.10 4.10 4.10 4.20 4.30 4.20 4.20 4.20 4.30 4.40 4.40 4.40 4.30 4.40 4.50
125
T.C. 31.7 31.9 29.3 33.2 37.0 32.6 33.1 29.5 33.3 37.3 33.5 34.2 29.7 33.4 37.7
S.C. 31.7 31.9 28.5 28.3 20.9 32.6 33.1 29.5 30.1 21.9 33.5 34.2 29.7 31.9 22.9
KW 4.40 4.40 4.30 4.50 4.60 4.50 4.50 4.40 4.50 4.70 4.60 4.60 4.50 4.60 4.80
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Air Handlers Coils T.C. S.C. KW
FC/MC/PC60 0.98 0.97 0.98
FC/MC62 0.99 0.98 0.98
UC60 0.97 0.95 0.97
AHE48D 0.99 0.97 0.93
AHE60D 1.00 0.99 0.92
AHR48D 0.98 0.95 0.98
AHR60D 0.98 0.97 0.97
AHV48D 0.99 0.96 0.94
AHV60D 0.99 0.99 0.94
AV*48 0.99 0.99 0.93
AV*60 1.00 0.99 0.93
MV16C FC60C 0.99 0.99 0.94
MV20D FC/MC60D 0.99 0.99 0.94
MV20D FC/MC62D 1.00 0.99 0.93
MX16C FC60C 1.00 0.99 0.92
MX20D FC/MC60D 1.00 1.00 0.91
MX20D FC/MC62D 1.01 1.00 0.91