Manual

975-0526-01-02 53
Troubleshooting
Symptom
The Truecharge2 Battery Charger will not perform equalization.
Possible Cause Solution
Battery is the wrong type, or set
to the wrong type to equalize.
Not all batteries are fully
charged.
An active fault is present on the
bank you are attempting to
equalize.
Determine if the battery type is set to
GEL or AGM. These battery types
cannot be equalized.
The charger will wait for all batteries to
be in float stage of three-stage charging
or rest stage of two-stage charging
before attempting to equalize (the ready
indicator LED will illuminate).
Clear the active fault by disconnecting
the AC power source and finding the
cause of the fault from “Interpreting
Fault and Warning Indicators” on page
43.
TC2 204060 Series BattChg Owners Guide.book Page 53 Friday, July 8, 2011 11:44 AM