INSTRUCTION MANUAL S13421 REVISION B INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
TABLE OF CONTENTS PAGE SECTION 1 – GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . PURPOSE OF MANUAL . . . . . . . . . . . . . . . . . SAFETY INSTRUCTION . . . . . . . . . . . . . . . . . HANDLING & STORAGE . . . . . . . . . . . . . . . . TEMPERATURE AND VENTILATION . . . . . . . INPUT VOLTAGE . . . . . . . . . . . . . . . . . . . . . . . GROUND CONNECTIONS . . . . . . . . . . . . . . . POWER WIRING . . . . . . . . . . . . . . . . . . . . . . . FIELD CONNECTION DIAGRAMS . . . . . . . . .
SECTION 1 – GENERAL 1.1 DESCRIPTION Fire Pump Package systems are custom built to the requirements provided by the purchaser. The AC Fire Pump Package is a complete fire protection system. Packaged Fire Pump Systems are designed in accordance with NFPA 20. Packges are factory hydrotested to internal quality standards and NFPA 20 requirements. 1.2 PURPOSE OF MANUAL 1.2.1 This manual is furnished to acquaint you with some of the practical ways to install, operate, and maintain this unit.
1.4.3 For periods of storage, the unit should be covered to prevent corrosion and contamination from dirt. It should be stored in a clean, dry location to prevent condensation as well as protected from freezing. After storage, again check that it is dry before applying power. Specific storage instructions must be followed in accordance with the respective equipment manufacturer’s recommendations. CAUTION: Extreme temperatures are to be avoided (below 32°F and above 110°F).
SECTION 2 – INSTALLATION 2.1 LOCATION 2.1.1 Locate the pumping system in a clean, well ventilated and properly drained location. It is recommended that the location selected facilitates ease of inspection, maintenance and service. Outside installations require protection from freezing. DANGER: Heavy load, may drop if not lifted properly. Do not lift the entire unit by component eyebolts.
SECTION 3 – OPERATION 3.1 PREPARATION 3.1.1 After package is installed and foundation bolts are tightened, check pump alignment. Refer to specific pump Installation, Operation & Maintenance manual for alignment procedures. 3.1.2 On packages with enclosures, inspect doors for proper alignment. Doors may become misaligned during shipping, handling and/or installation. Realign doors to provide and even 1/8" clearance between door and frame. 3.1.
3.2.4 PUMP ROTATION, 3 PHASE MOTORS ONLY. Check rotation of electric driven fire pump and jockey pump; refer to appropriate pump, driver and controller instruction manuals. WARNING: Rotating shafts can catch loose clothing. Do not operate the pump without all guards in place. FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE. 3.2.5 Relief valves are designed to protect the water system from damage resulting from excess system pressure.
APPENDIX A GENERAL – FINAL CHECK LIST ___ 1. Is the unit base properly leveled, grouted and secured? ___ 2. Are all lubrication points properly lubricated? ___ 4. Is the shut-off valve to the pump suction open? ___ 5. Is the shut-off valve on the discharge line open? ___ 6. Is the piping properly supported so as to prevent strains on unit? WARNING: Rotating shafts can catch loose clothing. Do not operate the pump without all guards in place.
APPENDIX B ELECTRICAL WIRING AND CONTROL SETTINGS – FINAL CHECK LIST ___ 1. Does the feeder line voltage correspond to the unit voltage? Check the unit nameplate or motor terminal connection. ___ WARNING: Electrical shock hazard. Inspect all electrical connections prior to powering the unit. Wiring connections must be made by a qualified electrician in accordance with all applicable codes, ordinances, and good practices.
Xylem 1) The tissue in plants that brings water upward from the roots; 2) a leading global water technology company. We’re 12,500 people unified in a common purpose: creating innovative solutions to meet our world’s water needs. Developing new technologies that will improve the way water is used, conserved, and re-used in the future is central to our work. We move, treat, analyze, and return water to the environment, and we help people use water efficiently, in their homes, buildings, factories and farms.