INSTRUCTION MANUAL IM245 RGS2012E1 S or E Retrofit Kit SUBMERSIBLE GRINDER PUMP INSTALLATION, OPERATION AND TROUBLESHOOTING MANUAL
SAFETY INSTRUCTIONS TO AVOID SERIOUS OR FATAL PERSONAL INJURY OR MAJOR PROPERTY DAMAGE, READ AND FOLLOW ALL SAFETY INSTRUCTIONS IN MANUAL AND ON EQUIPMENT. THIS MANUAL IS INTENDED TO ASSIST IN THE INSTALLATION AND OPERATION OF THIS UNIT AND MUST BE KEPT WITH THE UNIT. This is a SAFETY ALERT SYMBOL. When you see this symbol on the pump, the controller or in the manual, look for one of the following signal words and be alert to the potential for personal injury or property damage.
6. Check connections to make sure they are clean and dry. 7. Inspect connection, there are two styles round connectors- shown above and rectangular connectors. Ensure that the correct Retrofit Kit has been purchased for the style connection being replaced. 8. Remove bolts from cover plate of current unit 9. Close valve of current unit 10. Secure rope to hooks on cover. Lift Unit from basin. 11. Measure distance on Candy cane for setting up new retrofit – see below. 3.
TROUBLESHOOTING CHART WARNING FAILURE TO DISCONNECT AND LOCKOUT ELECTRICAL POWER BEFORE ATTEMPTING ANY Hazardous voltage SERVICE CAN CAUSE SHOCK, BURNS OR DEATH. SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION MOTOR NOT RUNNING Motor thermal protector tripped. Allow motor to cool. Insure minimum pump submergence. Clear debris from casing and impeller. Open circuit breaker or blown fuse. Determine cause, call a qualified electrician. Pump impeller binding or jammed. Check motor amp draw.
TROUBLESHOOTING CHART SYMPTOM PROBABLE CAUSE RECOMMENDED ACTION PUMP CYCLES CONSTANTLY Discharge check valve inoperative. Inspect, repair or replace as required. Sewage containment area too small. Consult with dealer. Liquid level controls defective or improperly positioned. Inspect, readjust or replace as required. Influent excessive for this size pump. Consult with dealer.
REPAIR PARTS 2 3 4 1 5 Item No. Major Components Extreme 1 RGS2010 Grinder E1 2 Junction Box with Electrical Adaptor 3 Check / Anti-Siphon Valve 4 Signal Master FS A2N03 5 Pump Master Plus FS A2E03 All dimensions ± 1/8 tolerance unless noted.
NOTES 7
GOULDS WATER TECHNOLOGY LIMITED WARRANTY This warranty applies to all water systems pumps manufactured by Goulds Water Technology. Any part or parts found to be defective within the warranty period shall be replaced at no charge to the dealer during the warranty period. The warranty period shall exist for a period of twelve (12) months from date of installation or eighteen (18) months from date of manufacture, whichever period is shorter.