9 Troubleshooting
9.1.1 List of Alarms for Command Option Attachable Type SERVOPACKs
9-2
9.1 Troubleshooting
When an alarm has been detected, the SERVOPACK stops the servomotor, and suspends motor operation.
When the SERVOPACK detects an alarm, the motor is stopped in accordance with the “alarm stopping
method” described below, and the alarm status is displayed.
Status Displays
Alarm Stopping Method
Gr.1: The servomotor is stopped according to the settings in Pn001.0 if an alarm occurs. Pn001.0 is factory-set
to stop the servomotor by applying the dynamic brake (DB).
Gr.2: The servomotor is stopped according to the setting in Pn00B.1 if an alarm occurs. Pn00B.1 is factory-set
to stop the servomotor by setting the speed reference to
0. The servomotor under torque control will
always use the Gr.1 method to stop. By setting Pn00B.1 to 1, the servomotor stops using the same
method as Gr.1. When coordinating a number of servomotors, use this alarm stop method to prevent
machine damage that may result due to differences in the stop method.
Alarm Reset Capability
Available: Removing the cause of alarm and then executing the alarm reset can clear the alarm.
N/A: Executing the alarm reset cannot clear the alarm.
9.1.1 List of Alarms for Command Option Attachable Type SERVOPACKs
The SERVOPACK alarm list is shown below.
For details on the causes of SERVOPACK alarms and the corrective action to take in response to them, refer to
the following manuals.
Σ
-V Series User's Manual Design and Maintenance Rotational Motor/Command Option Attachable Type
(SIEP S800000 60).
Σ
-V Series User's Manual Design and Maintenance Linear Motor/Command Option Attachable Type
(SIEP S800000 66).
SERVOPACK Panel Display The SERVOPACK alarm code is displayed.
LED
Green LED: Remains unlit
Red LED: Remains lit
Digital Operator The alarm code is displayed at the top left of the screen.
Response to the Alarm or Warning Read
Command (ALM)
Alarm code
Response to the Most Recent Error Read
Command (ERR)
No change
ALM Signal Becomes active (photocoupler OFF).
/WARN Signal No change
Alarm
Display
Alarm Name Meaning
Servomotor
Stop
Method
Alarm
Reset
Alarm Code Output
/ALO1 /ALO2 /ALO3
A.020
Parameter Checksum
Error
The data of the parameter in the SERVOPACK
is incorrect.
Gr.1 N/A
OFF
(open)
OFF
(open)
OFF
(open)
A.021 Parameter Format Error
The data format of the parameter in the SER-
VOPACK is incorrect.
Gr.1 N/A
A.022
System Checksum
Error
The data of the parameter in the SERVOPACK
is incorrect.
Gr.1 N/A
A.030
Main Circuit Detector
Error
Detection data for the main circuit is incorrect. Gr.1
Avail-
able
A.040 Parameter Setting Error
The parameter setting is outside the allowable
setting range.
Gr.1 N/A