User`s manual

10.2 Parameter List for Command Option Attachable Type SERVOPACKs
10-23
10
Appendix
Pn486
*2
Polarity Detection Reference Accel/Decel Time 0 to 100 1 ms 25 Immediately Tuning
Pn487
*2
Polarity Detection Constant Speed Time 0 to 300 1 ms 0 Immediately Tuning
Pn488
*2
Polarity Detection Reference Waiting Time 50 to 500 1 ms 100 Immediately Tuning
Pn48E
*2
Polarity Detection Range 1 to 65535 1 mm 10 Immediately Tuning
Pn490
*2
Polarity Detection Load Level 0 to 20000 1% 100 Immediately Tuning
Pn495
*2
Polarity Detection Confirmation Force Reference 0 to 200 1% 100 Immediately Tuning
Pn498
*2
Polarity Detection Allowable Error Range 0 to 30 1 deg 10 Immediately Tuning
Pn501
*1
Reserved (Do not change.) 10
Pn502
*1
Reserved (Do not change.)
20
Pn503
*1
Reserved (Do not change.)
10
Pn506
Brake Reference
-
Servo OFF Delay Time
0 to 50 10 ms 0 Immediately Setup
Pn507
*1
Brake Reference Output Speed Level 0 to 10000
1 min
-1
100 Immediately Setup
Pn508
Waiting Time for Brake Signal when Motor Run-
ning
10 to 100 10 ms 50 Immediately Setup
Pn509 Instantaneous Power Cut Hold Time 20 to 1000 1 ms 20 Immediately Setup
Pn50A Reserved (Do not change.) 8881
Pn50B Reserved (Do not change.) 8888
Pn50E Reserved (Do not change.) 3000
Pn50F Reserved (Do not change.) 1200
Pn510 Reserved (Do not change.) 0000
Pn511 Reserved (Do not change.) 8468
Pn512 Reserved (Do not change.) 0000
Pn513 Reserved (Do not change.) 0000
Pn517 Reserved (Do not change.) 0000
Pn51B
*1
Excessive Error Detection Level Between Servo-
motor and Load Position
0 to
1073741824
(2
30
)
1
reference
unit
1000 Immediately Setup
Pn51E Excessive Position Error Warning Level 10 to 100 1% 100 Immediately Setup
Pn520 Excessive Position Error Alarm Level
1 to
1073741823
(2
30
-1)
1
reference
unit
5242880 Immediately Setup
Pn522 Reserved (Do not change.) 1
Pn524 Reserved (Do not change.)
1073741824
––
Pn526 Excessive Position Error Alarm Level at Servo ON
1 to
1073741823
(2
30
-1)
1
reference
unit
5242880 Immediately Setup
Pn528
Excessive Position Error Warning Level at Servo
ON
10 to 100 1% 100 Immediately Setup
Pn529
*1
Speed Limit Level at Servo ON 0 to 10000
1 min
-1
10000 Immediately Setup
Pn52A
*1
Multiplier per One Fully-closed Rotation 0 to 100 1% 20 Immediately Setup
Pn52B Overload Warning Level 1 to 100 1% 20 Immediately Setup
Pn52C
Derating of Base Current at Detecting Overload of
Motor
10 to 100 1% 100 After restart Setup
∗1. Parameter exclusive for rotational servomotors
∗2. Parameter exclusive for linear servomotors
(cont’d)
Parameter
No.
Name
Setting
Range
Units
Factory
Setting
When
Enabled
Classification