User`s manual

3 SERVOPACK Installation
3.2.2 Installation Standards
3-4
3.2.2 Installation Standards
Observe the standards for mounting SERVOPACKs in control panels, including those for the mounting SER-
VOPACKs side by side in one control panel as shown in the following illustration.
SERVOPACK Mounting Orientation
Mount the SERVOPACK vertically to the base, with the front panel (the side with the panel operator display)
facing out.
Cooling
Refer to the following diagram and leave sufficient space for cooling by fans and natural convection.
Mounting SERVOPACKs Side by Side in a Control Panel
Leave sufficient space on each side and at the top and the bottom of each SERVOPACK. The width on each
side varies in accordance with the models of the SERVOPACKs used.
Also install cooling fans above the SERVOPACKs to disperse local pockets of warmer air around the SERVO-
PACKs .
Inside the Control Panel
The conditions inside the control panel should be the same as the environmental conditions of the SERVO-
PACK. Refer to 3.1.1 Installation Environment.
30 mm or more
40 mm or more
40 mm or more
Width varies with SERVOPACK model.
FanFan
SERVOPACK Model SGDV-
Side
Top and Bottom
Left Right
R70F, R90F, 2R1F, R70A, R90A, 1R6A, 2R8A 1 mm or more
40 mm or more
2R8F, 3R8A, 5R5A, 7R6A 1 mm or more 10 mm or more
120A, 180A, 200A, 330A, 470A, 550A, 590A, 780A,
1R9D, 3R5D, 5R4D, 8R4D, 120D, 170D, 210D, 260D,
280D, 370D
10 mm or more