2.3 SERVOPACK Installation
2-11
2
Installation
Mounting SERVOPACKs Side by Side in a Control Panel
Leave sufficient space on each side and at the top and the bottom of each SERVO-
PACK. The width on each side varies in accordance with the models of the SERVO-
PAC KS used.
Also install cooling fans above the SERVOPACKs to disperse local pockets of
warmer air around the SERVOPACKs.
Inside the Control Panel
The conditions inside the control panel should be the same as the environmental con-
ditions of the SERVOPACK. Refer to 2.1.2 SERVOPACK Installation Environment.
Fan
30 mm
or more
40 mm or more
40 mm or more
Width varies with
SERVOPACK model
Fan
SERVOPACK Model
SGDV-
Side
Top and bottom
Left Right
R70F, R90F, 2R1F,
R70A, R90A, 1R6A, 2R8A
1 mm or more
40 mm or more
2R8F, 3R8A, 5R5A, 7R6A 1 mm or more 10 mm or more
120A, 180A, 200A, 330A,
470A, 550A, 590A, 780A,
1R9D, 3R5D, 5R4D, 8R4D,
120D, 170D, 210D, 260D,
280D, 370D
10 mm or more