User`s manual

5 FUNCTIONS
21
Remote Output (from PLC to Inverter) Remote Input (from Inverter to PLC)
Device
No.
Signal Name Remarks (default)
Device
No.
Signal Name Remarks (default)
RY4
Terminal S5 multi-function
input terminal function
Multi-step speed
reference 1 (H1-03: 3)
RX4 Reserved
RY5
Terminal S6 multi-function
input terminal function
Multi-step speed
reference 2 (H1-04: 4)
RX5 Reserved
RY6
Terminal S7 multi-function
input terminal function
Jog Cmd (H1-05: 6) RX6
Terminal P1-PC
multi-function output
Zero speed (H2-02:1)
RY7
Terminal S8 multi-function
input terminal function
External baseblock RX7
Terminal P2-PC
multi-function output
Frequency agree
(H2-03:2)
RY8 Not used RX8 Not used
RY9 Inverter output shutoff RX9 Not used
RYA Not used RXA Not used
RYB
Motor actual rotational
speed /output frequency
changeover
*
RW
R1
data contents
changeover
RXB
Monitoring actual rotation
speed
RYC Monitor command RXC Monitoring
RYD
Frequency setting command
1
Writes to RAM RXD
Completion of frequency
setting 1
Writes to RAM
RYE
Frequency setting command
2
Saves Frequency
Reference 1
RXE
Completion of frequency
setting 2
Saves Frequency
Reference 1
RYF
Command code execution
request
— RXF
Completion of command
code execution
RY10
to
RY18
Not used
RX10
to
RX18
Not used
RY19
Multi-function I/O
allocation change request
— RX19
Completion of
multi-function I/O
allocation change
RY1A Error reset RX1A Error
RY1B Not used RX1B Remote station ready
RY1C Not used RX1C Not used
RY1D Not used RX1D Not used
RY1E Not used RX1E Not used
RY1F Not used RX1F Not used
* Enabled when the control mode is set to the V/f control with PG and flux vector control.
List of Remote Registers
From PLC to Inverter From Inverter to PLC
Device
No.
Signal Name
Execution
Request Flag
Device
No.
Signal Name
Execution
Request Flag
RW
W0
Monitor code
RYC RW
R0
Monitor data RXC
RW
W1
Setting frequency
RYD, RYE RW
R1
Output frequency --
RW
W2
Command code
RW
R2
Response code
RW
W3
Write data
RYF
RW
R3
Read data
RXF