User`s manual

5 FUNCTIONS
29
Extensive Command Codes
Command Code
Read Write
Name Data/Unit Description
0 Forward run Inverter runs forward.
1 Reverse run Inverter runs in reverse.
2 Terminal S3 input Multi-function input 3
3 Terminal S4 input Multi-function input 4
4 Terminal S5 input Multi-function input 5
5 Terminal S6 input Multi-function input 6
6 Terminal S7 input Multi-function input 7
7 Terminal S8 input Multi-function input 8
8 External fault (EF0) Drive stops when a fault occurs.
9 Fault reset Clears the inverter fault.
A Terminal S9 input Multi-function input 9
*1
B Terminal S10 input Multi-function input 10
*1
C Terminal S11 input Multi-function input 11
*1
D Terminal S12 input Multi-function input 12
*1
E Reserved Write in 0.
100h
Operation signal status bit
F Reserved Write in 0.
101h
Frequency reference 0 Hz to 400.0Hz Frequency set from the PLC
102h 202h Torque reference/torque
limit
-300.0% to +300.0% Limited by the setting of the
inverter limit.
103h 203h Torque compensation -300.0% to +300.0% Limited by the setting of the
inverter limit.
104h 204h Not used
105h 205h INV terminal 21 analog
output
-1540 to 1540 / -11V to 11V
106h 206h INV terminal 23 analog
output
-1540 to 1540 / -11V to 11V
0 Terminals M1-M2
output
Set H2-01 to F when writing data.
1 Terminals P1-PC
output
Set H2-02 to F when writing data.
2 Terminal P2-PC
output
Set H2-03 to F when writing data.
107h 207h INV terminal
multi-function output
bit
3 to F Fixed to 0 Write in 0.
108h to
10Fh
208h to
20Fh
Not used
0 Running ON while the inverter is running.
1 Zero speed ON while the motor is stopped.
2 Reverse running ON while running in reverse.
3 Inputting reset signal ON while reset signal is being
received.
4 Speed agree ON when the output frequency is
the same as the setting frequency.
5 Inverter ready ON when the inverter is ready to
run.
6 Minor fault ON while an alarm occurs in the
inverter.
7 Major fault ON while a fault occurs in the
inverter.
8 OPR error ON when the operator is
incorrectly connected.
9 Recovery from power
loss/momentary
power loss
ON when recovering from a
power loss or momentary power
loss.
A Remote/local ON when the operator has the
commanding right to run.
110h — Inverter status bit
B Terminals MA/MB
output
Terminals M1/M2 output status