User`s manual

7 TROUBLESHOOTING
35
The following table describes the failures, causes, and corrective actions that can be judged according to the LED of the
inverter CC-Link unit (SI-C unit) when the LED display of the master unit SW, M/S or PRM has been extinguished
(always set in the master unit), in the system configuration shown below.
LED Display
Remote Device Station(SI-C)
Master
Unit
Station
No. 1
Station
No. 2
Station
No. 3
Cause Corrective Action
L.RUN
SD
RD
L.ERR
L.RUN
SD
RD
L.ERR
L.RUN
SD
RD
L.ERR
The drive is operating
properly.
L.RUN
SD
RD
L.ERR
L.RUN
SD
RD
L.ERR
L.RUN
SD
RD
L.ERR
The SI-C card of station No.
1 is not attached correctly.
Check how it is attached
and reattach it correctly if
necessary.
L.RUN
SD
RD
L.ERR
L.RUN
SD
RD
L.ERR
L.RUN
SD
RD
L.ERR
The SI-C card of station No.
1 is defective. (Usually all
indicator lamps are
extinguished.)
An error may be displayed
in the inverter.
Replace the SI-C card.
L.RUN
SD
RD
L.ERR
L.RUN
SD
RD
L.ERR
L.RUN
SD
RD
L.ERR
L.RUN of station No. 2 and
other LEDs after it are
extinguished. The
transmission cable is
disconnected between
station No. 1 and 2 or is
removed from the terminal
block.
Refer to the LED lighting
status to look for the
disconnected part and then
correct it.
L.RUN
SD
RD
L.ERR
L.RUN
SD
RD
L.ERR
L.RUN
SD
RD
L.ERR
Transmission cable
shortcircuits.
Find the shortcircuiting
cable among the three
communications cables and
correct it.
TIME
LINE
or
TIME
LINE
L.RUN
SD
RD
L.ERR
L.RUN
SD
RD
L.ERR
L.RUN
SD
RD
L.ERR
Communications cable is
connected incorrectly.
Check the wiring in the
SI-C card's terminal block
and correct the incorrect
wiring.
Station
No. 1
Inverter
Master
Unit
Power
Station
No. 2
Inverter
Station
No. 3
Inverter
CPU
: Lit
: Flashing : Not lit : Either lit or not lit