How to check an error indicated by the LEDs.
L.RUN: Lit when the refleshed data is successfully received. Extinguished if data communications are
interrupted for a specified period of time.
SD : Lit when sending data is "1".
RD : Lit when detecting the receiving data carrier.
L.ERR: Lit when the local data has a CRC abort error.
The following table describes the causes and corrective actions of the failures that can be determined according to the
LED status of the SI-C card in a system configuration where one master is connected to one inverter.
LED Display
L.RUN SD RD L.ERR
Meaning Corrective Actions
Normal but an error is occurring. Remove the influence
of noise.
Communications are functioning normally.
Hardware error Turn the power
supply OFF and then
ON again.
Hardware error Turn the power
supply OFF and then
ON again.
A CRC error occurred, and the SI-C card
cannot replay.
Remove the influence
of noise.
Local data cannot be received. Confirm the PLC
program.
Hardware error Turn the power
supply OFF and then
ON again.
Hardware error Turn the power
supply OFF and then
ON again.
Polling response is made but an CRC error
occurred in refleshing the data.
Remove the influence
of noise.
Hardware error Turn the power
supply OFF and then
ON again.
Hardware error Turn the power
supply OFF and then
ON again.
Hardware error Turn ON the power
supply again.
Station
No. 1
Inverter
Master
Unit
Powe
r
CPU