Command Code Description Drive
Read Write BIT Display F7 G7
Alarm Description 2 Yes Yes
0 DEV Excessive Speed Deviation Yes Yes
1 PGO PG Disconnect Detection Yes Yes
2 OPR Digital Operator Connection Error Yes Yes
3 CE Memobus Communication Error Yes Yes
4 BUS Option Card Communication Error Yes Yes
5 CALL Waiting for Data via Communications Yes Yes
6 OL1 Motor Overload Yes Yes
7 OL2 Inverter Overload Yes Yes
8 - Not Used - -
9 EFO During Comm. Option Card External Fault Detection Yes Yes
A - Motor Switch During Run Yes Yes
101AH -
B-F - Not Used - -
Drive Status Yes Yes
0 1: During Run Yes Yes
1 1: While in Reverse Yes Yes
2 1: Drive Ready Yes Yes
3 1: Fault Yes Yes
4 1: Data Setting Error Yes Yes
5 1: Multi-Function Relay Output (M1-M2) ON Yes Yes
6 1: Multi-Function PH C1 Output (P1-PC) ON Yes Yes
7 1: Multi-Function PH C2 Output (P2-PC) ON Yes Yes
8 1: Multi-Function PH C3 Output (P3-C3) ON No Yes
9 1: Multi-Function PH C4 Output (P4-C4) ON No Yes
1020H -
A-F
N
ot Used - -
Fault Description Yes Yes
0 Overcurrent (OC) Ground (GF) Yes Yes
1 Main Circuit Overvoltage (OV) Yes Yes
2 Inverter Overload (OL) Yes Yes
3 Heat Sink Overheat, Inverter Internal Cooling Fan Stop (OH (OH1)) Yes Yes
4 Internal Braking Transistor Fault (Rr) Installed Braking Resistor Overheat (Rh) Yes Yes
5 Fuse Blown (PUF) Yes Yes
6 PID Feedback Command Loss (FBL) Yes Yes
7 External Fault (EF0, EF3~EF7) Yes Yes
8 Hardware Fault (CPF) Yes Yes
9 Motor Overload (OL1), Overtorque Detection 1 (OL3), Overtorque Detection 2
(OL4)
Yes Yes
A PG Disconnect Detection (PGO), Overspeed (OS), Excessive Speed Deviation
(DEV)
Yes Yes
B Main Circuit Undervoltage (UV) During Detection Yes Yes
C
Main Circuit Undervoltage / MC Operation Error (UV1) Control Power Supply
Fault (UV2)
Inrush Prevention Circuit Fault (UV3)
Yes Yes
D Output Phase (LF) Yes Yes
E Memobus Comm. Error Yes Yes
1021H -
F Operator Connection Error (OPR) Yes Yes
Data Link Status Yes Yes
0 While Saving Data Yes Yes
1 Not Used - -
2 Not Used - -
3 Upper/Lower Limit Fault Yes Yes
4 Data Compatibility Fault Yes Yes
1022H -
5-F Not Used - -