User`s manual

46
U2-xx Monitor Details
Command Code Description Drive
Read Write BIT F7 G7
1080H - U2-01 Current Fault Yes Yes
1081H - U2-02 Previous Fault Yes Yes
1082H - U2-03 Frequency Reference at Previous Fault Yes Yes
1083H - U2-04 Output Frequency at Previous Fault Yes Yes
1084H - U2-05 Output Current at Previous Fault Yes Yes
1085H - U2-06 Motor Speed at Previous Fault Yes Yes
1086H - U2-07 Output Voltage at Previous Fault Yes Yes
1087H - U2-08 DC Bus Voltage at Previous Fault Yes Yes
1088H - U2-09 Output Power at Previous Fault Yes Yes
1089H - U2-10 Torque Reference at Previous Fault Yes Yes
Input Terminal Status during Fault Yes Yes
0 1: Control Circuit Terminal S1 Closed Yes Yes
1 1: Control Circuit Terminal S2 Closed Yes Yes
2 1: Control Circuit Terminal S3 Closed Yes Yes
3 1: Control Circuit Terminal S4 Closed Yes Yes
4 1: Control Circuit Terminal S5 Closed Yes Yes
5 1: Control Circuit Terminal S6 Closed Yes Yes
6 1: Control Circuit Terminal S7 Closed Yes Yes
108AH - U2-11
7 Not Used - -
Output Terminal Status when Fault Occurs Yes Yes
0 1: Control Circuit Terminal M1-M2 Closed Yes Yes
1 1: Control Circuit Terminal P1 Closed Yes Yes
2 1: Control Circuit Terminal P2 Closed Yes Yes
3-6 Not Used - -
108BH - U2-12
7 1: Terminal MA/ MB-MC Closed Yes Yes
Run Status when Fault Occurs Yes Yes
0 1: During Run Yes Yes
1 1: At Zero Speed Yes Yes
2 1: While in REV Yes Yes
3 1: Reset Signal During Input Yes Yes
4 1: During Speed Agree Yes Yes
5 1: Drive Ready Yes Yes
6 1: Alarm Yes Yes
108CH - U2-13
7 1: Fault Yes Yes
108DH - U2-14 Cumulative Operation Time at Previous Fault Yes Yes
U3-xx Monitor Details
Command Code Drive
Read Write
Description
F7 G7
1090H - U3-01 Most Recent Fault (see the following page) Yes Yes
1091H - U3-02 2nd Most Recent Fault (see the following page) Yes Yes
1092H - U3-03 3rd Most Recent Fault (see the following page) Yes Yes
1093H - U3-04 4th Most Recent Fault (see the following page) Yes Yes
1094H - U3-05 Cumulative Operation Time at Most Recent Fault Yes Yes
1095H - U3-06 Cumulative Operation Time at 2nd Most Recent Fault Yes Yes
1096H - U3-07 Cumulative Operation Time at 3rd Most Recent Fault Yes Yes
1097H - U3-08 Cumulative Operation Time at 4th Most Recent Fault Yes Yes