Instruction manual

6. Programming Features
115
Simultaneous Broadcasting Data (available only for write in)
Bit signals not defined as the broadcast operation signals are used as
the local station data signals.
Monitor Data (available only for read out)
Register
No.
Bit Description
0001H
0 RUN command 1: Run 0: Stop
1 Reverse run 1: Reverse run 0: Forward run
2 (Not used)
3 (Not used)
4 External fault 1: Fault (EFO)
5 Fault reset 1: Fault reset command
6-F (Not used)
0002H
Frequency reference 30000/100 % fixed unit
(Data is converted into 0.01 Hz inside the Inverter, and fractions
are rounded off.)
Register
No.
Bit Description
0020H
Status signal
0 RUN command 1: Run 0: Stop
1 Reverse run 1: Reverse run 0: Forward run
2
Inverter operation
ready
1: Ready 0: Not ready
3 Fault 1: Fault
4 Data setting error 1: Error
5 Multi-function output 1 (1: MA ON 0: MA OFF)
6 Multi-function output 2 (1: P1 ON 0: P1 OFF)
7 Multi-function output 3 (1: P2 ON 0: P2 OFF)
8-F (Not used)