Instruction manual

6. Programming Features
119
* Communications error contents are saved until fault reset is input.
(Reset is enabled during run.)
Storing Constants [ENTER Command] (can be written only.)
When a constant is written from the PLC by communications, the con-
stant is written to the constant data area on the RAM in the VS-606V7.
ENTER command is a command to write the constant data on the RAM
to the non-volatile memory in the VS-606V7. This ENTER command
is executed when data, regardlesss of the value, is written to register
number 0900H. With the factory setting, an ENTER command is
accepted only while the Inverter is stopped. By changing constant
n170, an ENTER command can be accepted even while the Inverter is
running.
0038H
PID feedback value (100 % /Input equivalent to max. output frequency ;
10/1 % ; without sign)
0039H PID input value (±100 %/±Max. output frequency ; 10/1 % ; with sign)
003AH PID output value (±100 %/±Max. output frequency ; 10/1 % ; with sign)
003BH-
003CH
Reserved
003DH
Communications error
0 CRC error
1 Data length fault
2 (Not used)
3 Parity error
4 Overrun error
5 Framing error
6 Timeover
7 (Not used)
003EH-
00FFH
Reserved
Register
No.
Name Contents Setting
Range
Factory
Setting
0900H ENTER
command
Write in constant data to non-
volatile memory (EEPROM)
0000H to
FFFFH
-
Register
No.
Bit Description