8. Fault Diagnosis
171
Protective
Operation
Output is
turned OFF
and motor
coasts to a
stop.
PF (Main circuit voltage
fault)
The main circuit’s DC voltage
oscillated in an irregular way
when not in regenerative op-
eration.
Open phase of input
supply
• Momentary power loss
• Excessive fluctuation in
input supply voltage
Unbalanced line voltage
Check the following:
Main circuit power sup-
ply connections
• Power supply voltage
• Terminal screws:
Loose?
LF (Output open phase)
An open phase occurred in
Inverter output.
Disconnection in output
cable
Disconnection in motor
windings
Loose output terminal
screws
Check the following:
Disconnection in output
wirings
• Motor impedance
• Terminal screws:
Loose?
UL3 (Undertorque de-
tection)
When V/f mode is selected:
The Inverter’s output current
was less than the Under-
torque Detection Level
(n118).
When vector mode is select-
ed:
The output current or output
torque was less than the de-
tection level (n097 to n118).
Operation when undertorque
is detected will be determined
by the setting in n117.
Check the setting in
n118.
Check the operating
conditions, and remove
the cause.
Fault Display Inverter
Status
Description Causes and Corrective
Actions
Digital
Operator
RUN (Green)
ALARM (Red)