Instruction manual

174
* To display or clear the fault history, refer to page 50.
Stops ac-
cording to
constant.
STP (Emergency stop)
The Inverter stopped accord-
ing to constant n005 after re-
ceiving the emergency stop
fault signal.
Check the following:
• NO/NC contact selec-
tion (constant).
Wiring is made properly.
Signal is not input from
the PLC.
FBL (PID feedback loss
detection)
PID feedback value dropped
below the detection level.
When PID feedback loss is
detected, the Inverter oper-
ates according to the n136
setting.
Check the mechanical sys-
tem and correct the cause,
or increase the value of
n137.
Option card communica-
tions fault
A communication error oc-
curred in the mode where the
communication option card
was used and a run com-
mand or frequency reference
was input from the PLC.
Check the following:
• Communications
devices or communica-
tions signals.
PLC is not faulty.
Transmission cable is
connected properly.
Wiring is made properly.
Any loose terminal
screws do not result in
improper contact.
• Communication option
card is not inserted cor-
rectly.
Protective
Operation
Output is
turned OFF
and motor
coasts to a
stop.
• Insufficient power
supply voltage
Control power sup-
ply fault
• Hardware fault
Check the following:
• Power supply voltage
Main circuit power sup-
ply connections
• Terminal screws: Loose?
• Control sequence.
• Replace the Inverter.
Fault Display Inverter
Status
Description Causes and Corrective
Actions
Digital
Operator
RUN (Green)
ALARM (Red)
or
(OFF)