9. Specifications
179
Motor Overload
Protection
Electronic thermal overload relay
Instantaneous
Overcurrent
Motor coasts to a stop at approx. 250% or more of Inverter rated current
Overload Motor coasts to a stop after 1 minute at 150% of Inverter rated output
current
Overvoltage Motor coasts to a stop if DC bus voltage exceed 410 V
Undervoltage Stops when DC bus voltage is approx. 200 V or less (approx. 160 V or
less for single-phase series).
Momentary Power Loss Following items are selectable: Not provided (stops if power loss is 15
ms or longer), continuous operation if power loss is approx. 0.5 s or
shorter, continuous operation.
Heatsink Overheat Protected by electronic circuit.
Stall Prevention Level Can be set individual level during acceleration/constant-speed opera-
tion, provided/not provided available during deceleration.
Cooling Fan Fault Protected by electronic circuit (fan lock detection).
Ground Fault
*4
Protected by electronic circuit (overcurrent level).
*3
Power Charge
Indication
ON until the DC bus voltage becomes 50 V or less. RUN indicator stays
ON or Digital Operator indicator stays ON.
Multi-function
Input
Seven of the following input signals are selectable: Forward run com-
mand, reverse run command, forward/reverse run (3-wire sequence),
fault reset, external fault, multi-step speed operation, JOG command,
acceleration/deceleration time select, external baseblock, SPEED
SEARCH command, ACCELERATION/DECELERATION HOLD com-
mand, LOCAL/REMOTE selection, communication/control circuit termi-
nal selection, emergency stop fault, emergency stop alarm, UP/DOWN
command, self-test, PID control cancel, PID integral reset/hold, Inverter
overheat alarm
Multi-function
Output
*5
Following output signals are selectable (1 NO/NC contact output, 2
photocoupler outputs):
Fault, running, zero speed, frequency agree, frequency detection,
overtorque detection, undervoltage detection, minor error, baseblock,
operating mode, Inverter run ready, fault retry, UV, speed search, data
output through communications, PID feedback loss detection, frequency
reference loss, Inverter overheat alarm
Standard Functions Voltage vector control, full-range automatic torque boost, slip compensa-
tion, DC injection braking current/time at startup/stop, frequency refer-
ence bias/gain, MEMOBUS communications (RS-485/422, max. 19.2 k
bps), PID control, energy-saving control, constant copy, frequency refer-
ence with built-in potentiometer, unit selection for frequency reference
setting/display, multi-function analog input
Voltage Class 200 V single-/3-phase
Model
CIMR-
V7T

3-phase 20P1 20P2 20P4 20P7 21P5 22P2 23P7 25P5 27P5
Single-phase B0P1 B0P2 B0P4 B0P7 B1P5 B2P2 B3P7 - -
Protective FunctionsOutput Functions
Input SignalsOutput Signals