Motor Overload Protec-
tion
Electronic thermal overload relay
Instantaneous
Overcurrent
Motor coasts to a stop at approx. 250% or more of Inverter rated current
Overload Motor coasts to a stop after 1 minute at 150% of Inverter rated output
current
Overvoltage Motor coasts to a stop if DC bus voltage exceed 820 V
Undervoltage Stops when DC bus voltage is approx. 400 V or less
Momentary Power Loss Following items are selectable: Not provided (stops if power loss is 15
ms or longer), continuous operation if power loss is approx. 0.5 s or
shorter, continuous operation.
Heatsink Overheat Protected by electronic circuit.
Stall Prevention Level Can be set to individual levels during acceleration/constant-speed oper-
ation, provided/not provided available during deceleration.
Cooling Fan Fault Protected by electronic circuit (fan lock detection).
Ground Fault
*4
Protected by electronic circuit (overcurrent level).
*3
Power Charge Indica-
tion
ON until the DC bus voltage becomes 50 V or less. Charge LED is pro-
vided.
Multi-function
Input
Seven of the following input signals are selectable: Forward run com-
mand, reverse run command, forward/reverse run (3-wire sequence),
fault reset, external fault, multi-step speed operation, JOG command,
acceleration/deceleration time select, external baseblock, SPEED
SEARCH command, ACCELERATION/DECELERATION HOLD com-
mand, LOCAL/REMOTE selection, communication/control circuit termi-
nal selection, emergency stop fault, emergency stop alarm, UP/DOWN
command, self-test, PID control cancel, PID integral reset/hold, Inverter
overheat alarm
Multi-function
Output
*5
Following output signals are selectable (1 NO/NC contact output, 2
photocoupler outputs):
Fault, running, zero speed, frequency agree, frequency detection,
overtorque detection, undertorque detection, minor error, baseblock, op-
erating mode, Inverter run ready, fault retry, UV, speed search, data out-
put through communications, PID feedback loss detection, frequency
reference loss, Inverter overheat alarm
Standard Functions Voltage vector control, full-range automatic torque boost, slip compensa-
tion, DC injection braking current/time at startup/stop, frequency refer-
ence bias/gain, MEMOBUS communications (RS-485/422, max. 19.2
kbps), PID control, energy-saving control, constant copy, frequency ref-
erence with built-in potentiometer, unit selection for frequency reference
setting/display, multi-function analog input
Voltage Class 400 V 3-phase
Model
CIMR-
V7T

3-phase 40P2 40P4 40P7 41P5 42P2 43P0 43P7 45P5 47P5
Single-phase ---------
Protective FunctionsOutput Functions
Input SignalsOutput Signals