Instruction manual

9. Specifications
183
* 1. Based on a standard 4-pole motor for max. applicable motor output.
* 2. Shows deceleration torque for uncoupled motor decelerating from 60 Hz
with the shortest possible deceleration time.
* 3. The operation level becomes approx. 50% of Inverter rated output current
in case of Inverters of 5.5 kW or 7.5 kW
* 4. Since grounding in the motor winding is assumed, low-resistance ground-
ing in the motor cable or terminal block cannot be protected.
* 5. Minimum permissible load: 5 VDC, 10 mA (as reference value)
* 6. 0P1 to 3P7 are of IP20. Be sure to remove the top and bottom covers
when Inverter 5P5 or 7P5 of open chassis mounting type is used.
* 7. NEMA 1 of 0P1 to 3P7 is optional, while NEMA 1 of 5P5 and 7P5 is pro-
vided as standard.
* 8. Temperature during shipping (for short period).
Status Indica-
tors
RUN and ALARM provided as standard indicators
Digital Operator
(JVOP-140)
Provided for monitor frequency reference, output frequency, output cur-
rent
Terminals Main circuit: screw terminals
Control circuit: plug-in screw terminal
Wiring Distance
between Inverter and
Motor
100 m or less
Enclosure
Open chassis (IP20, IP00)
*6
, or enclosed wall-mounted NEMA 1 (TYPE
1)
*7
Cooling Method Cooling fan is provided for the following models:
400 V, 1.5 kW or larger Inverters (3-phase)
Other models are self-cooling.
Ambient Temperature Open chassis (IP20, IP00): 10 to 50°C
Enclosed wall-mounted NEMA 1 (TYPE 1): 10 to 40°C
(not frozen)
Humidity 95% or less (non-condensing)
Storage Temperature
*8
20 to 60°C
Location Indoor (free from corrosive gases or dust)
Elevation 1,000 m or less
Vibration
Up to 9.8 m/s
2
(1G) at 10 to less than 20 Hz,
up to 2 m/s
2
(0.2G) at 20 to 50 Hz
Voltage Class 400 V 3-phase
Model
CIMR-
V7T

3-phase 40P2 40P4 40P7 41P5 42P2 43P0 43P7 45P5 47P5
Single-phase ---------
Other Functions
Indications
Environmental Conditions