Recommended Peripheral Devices
It is recommended that the following peripheral devices be mounted
between the AC main circuit power supply and VS-606V7 input termi-
nals R/L1, S/L2, and T/L3.
• MCCB (Molded-case Circuit Breaker)/Fuse:
Always connect for wiring protection.
• Magnetic Contactor:
Mount a surge suppressor on the coil. (Refer to the table shown
below.) When using a magnetic contactor to start and stop the
Inverter, do not exceed one start per hour.
Recommended MCCB Magnetic Contactors and Fuses
200 V 3-phase
200 V Single-phase
VS-606V7 Model V7**
20P1
V7**
20P2
V7**
20P4
V7**
20P7
V7**
21P5
V7**
22P2
V7**
23P7
V7**
25P5
V7**
27P5
Capacity (kVA) 0.3 0.6 1.1 1.9 3.0 4.2 6.7 9.5 13.0
Rated Output Current (A) 0.8 1.6 3 5 8 11 17.5 25.0 33.0
MCCB type NF30
(MITSUBISHI)
5 A 5 A 5 A 10 A 20 A 20 A 30 A 50 A 60A
Magnetic contactor
(Fuji Electric FA
Components &
Systems)
Without
reactor
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-N1
(26A)
SC-N2
(35A)
SC-
N2S
(50A)
SC-N3
(65A)
With
reactor
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-N1
(26A)
SC-N2
(35A)
SC-
N2S
(50A)
Fuse (UL Class RK5) 5 A 5 A 5 A 10 A 20 A 20 A 30 A 50 A 60 A
VS-606V7 Model
V7**
B0P1
V7**
B0P2
V7**
B0P4
V7**
B0P7
V7**
B1P5
V7**
B2P2
V7**
B3P7
Capacity (kVA) 0.30.61.11.93.04.26.7
Rated Output Current (A) 0.8 1.6 3 5 8 11 17.5
MCCB type NF30, NF50
(MITSUBISHI)
5 A 5 A 10 A 20 A 20 A 40 A 50 A
Magnetic contactor
(Fuji Electric FA
Components &
Systems)
Without
reactor
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-N2
(35A)
SC-N2
(35A)
SC-N2S
(50A)
With
reactor
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-N1
(26A)
SC-N2
(35A)
SC-N2S
(50A)