Instruction manual

194
• 400 V 3-phase
Surge Suppressors
• Ground Fault Interrupter:
Select a ground fault interrupter not affected by high frequencies. To
prevent malfunctions, the current should be 200 mA or higher and
the operating time 0.1 s or longer.
Example:
• NV series by Mitsubishi Electric Co., Ltd. (manufactured in 1988
and after)
• EGSG series by Fuji Electric Co., Ltd. (manufactured in 1984 and
after)
Fuse (UL Class RK5) 5 A 5 A 10 A 20 A 20 A 40 A 50 A
VS-606V7 Model V7**
40P2
V7**
40P4
V7**
40P7
V7**
41P5
V7**
42P2
V7**
43P0
V7**
43P7
V7**
45P5
V7**
47P5
Capacity (kVA) 0.9 1.4 2.6 3.7 4.2 5.5 6.6 11.0 14.0
Rated Output Current (A) 1.2 1.8 3.4 4.8 5.5 7.2 8.6 14.8 18.0
MCCB type NF30, NF50 (MIT-
SUBISHI)
5 A 5 A 5 A 10 A 10 A 20 A 20 A 30 A 30 A
Magnetic contactor
(Fuji Electric FA
Components &
Systems)
Without
reactor
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-4-0
(18A)
SC-N1
(26A)
SC-N2
(35A)
SC-N2
(35A)
With
reactor
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-N1
(26A)
SC-N2
(35A)
Fuse (UL Class RK5) 5 A 5 A 5 A 10 A 10 A 20 A 20 A 30 A 30 A
Model
DCR2-
Specifications Code No.
200 V to
230 V
Large size magnetic
contactors
50A22E 250 VAC
0.5 µF 200
C002417
Control relays
MY-2, -3 (OMRON)
HH-22, -23 (FUJI)
MM-2, -4 (OMRON)
10A25C 250 VAC
0.1 µF 100
C002482
VS-606V7 Model
V7**
B0P1
V7**
B0P2
V7**
B0P4
V7**
B0P7
V7**
B1P5
V7**
B2P2
V7**
B3P7
Surge Suppressors
Coils and Relays