Instruction manual

9. Specifications
199
Second Functions (Constants n050 to n079)
046
#4
012E Frequency reference bias
accel/decel rate (UP/DOWN
command 2)
0, 1 - 0 Yes -
047
#4
012F Frequency reference bias
operation mode selection
(UP/DOWN command 2)
0, 1 - 0 Yes -
048
#4
0130 Frequency reference bias
value (UP/DOWN command
2)
-99.9% to
100.0%
(n011/
100%)
0.1% 0.0% No -
049
#4
0131 Analog frequency reference
fluctuation limit level (UP/
DOWN command 2)
0.1% to
100.0%
(n011/100%)
0.1% 1.0% Yes -
No. Register
No. for
Trans-
mission
Name Setting Range Setting Unit Factory
Setting
Change
during
Opera-
tion
User
Set-
ting
Ref.
Page
050 0132 Multi-function Input Selection
1 (Terminal S1)
1 to 25, 26#3,
27#3
-1No90
051 0133 Multi-function Input Selection
2 (Terminal S2)
1 to 25, 26#3,
27#3
-2No90
052 0134 Multi-function Input Selection
3 (Terminal S3)
1 to 25, 26#3,
27#3
-3No90
053 0135 Multi-function Input Selection
4 (Terminal S4)
1 to 25, 26#3,
27#3
-5No90
054 0136 Multi-function Input Selection
5 (Terminal S5)
1 to 25, 26#3,
27#3
-6No90
055 0137 Multi-function Input Selection
6 (Terminal S6)
1 to 25, 26#3,
27#3
-7No90
056 0138 Multi-function Input Selection
7 (Terminal S7)
1 to 25, 26#3,
27#3, 34, 35,
36#4
-10No 90
057 0139 Multi-function Output Selec-
tion 1
0 to 7, 8#3,
9#3, 10 to 19,
20#3, 21#3
-0No95
058 013A Multi-function Output Selec-
tion 2
0 to 7, 8#3,
9#3, 10 to 19,
20#3, 21#3
-1No95
059 013B Multi-function Output Selec-
tion 3
0 to 7, 8#3,
9#3, 10 to 19,
20#3, 21#3
-2No95
No. Register
No. for
Trans-
mission
Name Setting Range Setting Unit Factory
Setting
Change
during
Opera-
tion
User
Set-
ting
Ref.
Page