127 017F Frequency Reference 16 0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz Yes 65
128 0180 PID Control Selection 0 to 8 - 0 No 129
129 0181 PID Feedback Gain 0.00 to 10.00
Hz
0.01 1.00 Yes 132
130 0182 Proportional Gain (P) 0.0 to 25.0 0.1 1.0 Yes 131
131 0183 Integral Time (I) 0.0 to 360.0 s 0.1 s 1.0 s Yes 131
132 0184 Derivative Time (D) 0.00 to 2.50 s 0.01 s 0.00 Yes 131
133 0185 PID Offset Adjustment 100% to
100%
1% 0% Yes 131
134 0186 Upper Limit of Integral Values 0% to 100% 1% 100% Yes 131
135 0187 Primary Delay Time Constant
for PID Output
0.0 to 10.0 s 0.1 s 0.0 s Yes 132
136 0188 Selection of PID Feedback
Loss Detection
0 to 2 - 0 No 133
137 0189 PID Feedback Loss Detection
Level
0% to 100% 1% 0% No 133
138 018A PID Feedback Loss Detection
Time
0.0 to 25.5 s 0.1 s 1.0 s No 133
139 018B Energy-saving Control Selec-
tion (V/f Control Mode)
0, 1 - 0 No 123
140 018C Energy-saving Coefficient K2 0.0 to 6550 0.1 (Note 7) No 123
141 018D Energy-saving Control Voltage
Lower Limit at 60 Hz
0% to 120% 1% 50% No 124
142 018E Energy-saving Control Voltage
Lower Limit at 6 Hz
0% to 25% 1% 12% No 124
143 018F Power Average Time 1 to 200 1 = 24 ms 1 (24 ms) No 125
144 0190 Search Operation Voltage
Limit
0% to 100% 1% 0% No 125
145 0191 Search Operation Voltage
Step at 100%
0.1% to 10.0% 0.1% 0.5% No 125
146 0192 Search Operation Voltage
Step at 5%
0.1% to 10.0% 0.1% 0.2% No 125
149 0195 Pulse Train Input Scaling 100 to 3300 1 = 10 Hz 2500
(25 kHz)
No 99
No. Register
No. for
Trans-
mission
Name Setting Range Setting Unit Factory
Setting
Change
during
Opera-
tion
User
Set-
ting
Ref.
Page