Instruction manual

206
Note: 1. Not initialized by constant initialization.
2. Upper limit of setting range and factory setting are doubled for 400 V
Class.
3. Depends on Inverter capacity. Refer to the next page.
4. Depends on Inverter capacity. Refer to page 82.
5. Factory setting of the model with JVOP-147 Digital Operator (with-
out potentiometer) is 1. Setting can be set to 0 by constant initializa-
tion.
6. When control mode selection (n002) is changed, factory setting corre-
sponds to the control mode. Refer to the next page.
7. Depends on Inverter capacity. Refer to page 123.
8. Constant that is provided for 5.5 kW and 7.5 kW Inverters of 200-V
and 400-V classes
9. 1 (Enabled) for 5.5 kW and 7.5 kW Inverters of 200-V and 400-V
classes
171
#4
01AB Frequency reference bias up-
per limit (UP/DOWN com-
mand 2)
0.0 to 100.0%
(n011/100%)
0.1% 0.0% Yes -
172
#4
01AC Frequency reference bias low-
er limit (UP/DOWN command
2)
-99.9 to 0.0%
(n011/100%)
0.1% 0.0% Yes -
173
#3
01AD DC Injection Braking Propor-
tional Gain
1 to 999 1 = 0.001 83
(0.083)
No -
174
#3
01AE DC Injection Braking Integral
Time Constant
1 to 250 1 = 4 ms 25 (100
ms)
No -
175
#1
01AF Reducing Carrier Frequency
Selection at Low Speed
0, 1 -
0
*9
No 84
176 01B0 Constant Copy Function Se-
lection
rdy, rEd, Cpy,
vFy, vA, Sno
- rdy No 136
177 01B1 Constant Read Selection Pro-
hibit
0, 1 - 0 No 137
178 01B2 Fault History Stores, dis-
plays most
recent 4
alarms
Setting
disabled
-No 50
179 01B3 Software Version No. Displays
lower-place 4
digits of soft-
ware No.
Setting
disabled
-No -
No. Register
No. for
Trans-
mission
Name Setting Range Setting Unit Factory
Setting
Change
during
Opera-
tion
User
Set-
ting
Ref.
Page