Instruction manual

48
Monitoring
The following items can be monitored using U constants.
* 1. The status indicator is not turned ON.
* 2. Refer to the next page for input/output terminal status.
* 3. The display range is from 99.9 to 99.99 kW.
When regenerating, the output power will be displayed in units of
0.01 kW when
9.99 kW or less and in units of 0.1 kW when more
than
9.99 kW.
Constant
No.
Name Unit Description
U-01 Frequency Reference
(FREF)*
1
Hz Frequency reference can be monitored.
(Same as FREF)
U-02 Output Frequency
(FOUT)*
1
Hz Output frequency can be monitored.
(Same as FOUT)
U-03
Output Current (IOUT)*
1
A Output current can be monitored.
(Same as IOUT)
U-04 Output Voltage V Output voltage can be monitored.
U-05 DC Voltage V Main circuit DC voltage can be monitored.
U-06
Input Terminal Status*
2
- Input terminal status of control circuit terminals can
be monitored.
U-07
Output Terminal Status*
2
- Output terminal status of control circuit terminals can
be monitored.
U-08 Torque Monitor % The amount of output torque per rated torque of the
motor can be monitored. When V/f control mode is
selected, “---” is displayed.
U-09 Fault History
(Last 4 Faults)
- The last four fault history records are displayed.
U-10 Software No. - Software number can be checked.
U-11
Output Power*
3
kW Output power can be monitored.
U-13 Cumulative
operation time *
4
×10 H Cumulative operation time can be monitored in units
of 10 hours.
U-15
Data Reception Error*
5
- Contents of MEMOBUS communication data recep-
tion error can be checked.
(Contents of transmission register No. 003DH are
the same.)
U-16
PID Feedback*
6
% Input 100(%)/Max. output frequency or equivalent
U-17
PID Input*
6
% ±100(%)/± Max. output frequency
U-18
PID Output*
6
% ±100(%)/± Max. output frequency
U-19 Frequency reference
bias monitor *
7
% Bias can be monitored when UP/DOWN command 2
is used.