Fault History Display Method
When U-09 is selected, a four-digit box is displayed. The three digits
from the right show the fault description, and the digit on the left shows
the order of fault (from one to four). Number 1 represents the most
recent fault, and numbers 2, 3, 4 represent the other faults, in ascending
order of fault occurrence.
Example:
yyyyyy 4-digit number
: Order of fault (1 to 4)
 : Fault description
"---" is displayed if there is no fault.
(Refer to Chapter 8. Fault Diagnosis for details.)
Switching Fault History Records
The fault that is displayed can be changed using the or key.
Clearing the Fault History
Set constant n001 to 6 to clear the fault history. The display will return
to n001 after 6 is set.
Note: Initializing the constants (n001=8, 9) also clears the fault history.
Setting and Referencing Constants
The following diagram shows how to select and change constants.
REMOTE/LOCAL
selection
Constant
No./
data
n003
Operation
reference
selection
Factory setting: 0
Operator reference
Set to 1
Control circuit
terminal reference
(flashing at changing)
Data set
Return to
constant No.
display after
1 second
Setting n003 (RUN command selection)