Instruction manual

6. Programming Features
83
* Reduction of the current is not necessary.
1. Reduce the continuous output current when changing the
carrier frequency to 4 (10 kHz) for 200 V Class (1.5 kW
or more) and 400 V Class Inverters. Refer to the table
above for the reduced current.
Operation Condition
• Input power supply voltage:
3-phase 200 to 230 V (200 V Class)
Single-phase 200 to 240 V (200 V Class)
3-phase 380 to 460 V (400 V Class)
• Ambient temperature:
10 to 50°C
(Protection structure: open chassis type IP20,
IP00)
10 to 40°C
(Protection structure: enclosed wall-mounted type
NEMA 1 (TYPE 1))
200 V
Single-
phase or
3-phase
5.5 3 7.5 25 23
7.5 3 7.5 33 30
400 V
3-phase
0.2 3 7.5 1.2 1.0
0.4 3 7.5 1.8 1.6
0.75 3 7.5 3.4 3.0
1.5 3 7.5 4.8 4.0
2.2 3 7.5 5.5 4.8
3.0 3 7.5 7.2 6.3
3.7 3 7.5 8.6 8.1
5.5 3 7.5 14.8 *
7.5 3 7.5 18 17
Voltage
Class (V)
Capacity
(kW)
Factory Setting Maximum
Continuous
Output Current
(A)
Reduced
Current
(A)Setting Carrier Frequency
(kHz)
NOTE