Factory Settings
Terminal Functions for 3-wire Sequence Selection
When 0 is set for terminal S3 (n052), terminal S1 is the RUN command,
terminal S2 is the STOP command, and terminal S3 is the FWD/REV
RUN command.
To select the 3-wire sequence, set terminal S3 (n052)
to 0.
Failure to observe this warning may result in injury.
LOCAL/REMOTE Selection (Setting: 17)
Select the operation reference from either the Digital Operator or from
the settings of the RUN Command Selection (n003) and Frequency Ref-
erence Selection (n004). The LOCAL/REMOTE Selection can be used
only when stopped.
Open: Run according to the setting of RUN Command Selection
(n003) or Frequency Reference Selection (n004).
Closed: Run according to the frequency reference and RUN command
from the Digital Operator.
No. Terminal Factory Setting Function
n050 S1 1 FORWARD RUN command
(2-wire sequence)
n051 S2 2 REVERSE RUN command
(2-wire sequence)
n052 S3 3 External fault (NO contact input)
n053 S4 5 Fault reset
n054 S5 6 Multi-step speed reference 1
n055 S6 7 Multi-step speed reference 2
n056 S7 10 JOG command
RUN Command
(Run when Closed)
STOP Command
(Stop when Open)
FWD/REV Run Selection
FWD Run When Open
REV Run When Closed
RUN SW
(NO Contact)
STOP SW
(NC Contact)
VS-606V7