87
Other Functions Chapter 6-7
When the RUN command for forward or reverse rotation is input, the
Inverter will start operating at the lower limit regardless of whether the UP/
DOWN command is input or not.
When the UP/DOWN function and inching frequency command are both
assigned to multi-function inputs, an inching frequency command input
will have the highest priority.
If n62 for UP/DOWN command frequency memory is set to 1, the output
frequency held by the UP/DOWN function for 5 s or more will be stored in
the memory. The output frequency will be held by the UP/DOWN function
when both UP and DOWN commands are ON or OFF together.
6-7-8 Error History (n78)
The J7AZ stores information on the latest error.
The information on the latest error recorded is displayed by pressing the
Enter Key after n78 for error history is displayed.
The details of the information are the same as that obtained from the
multi-function monitor U09.
Note The information is read only.
Display Example
To clear the error history, set n01 for parameter write-prohibit selection/
parameter initialization to 6.
n78 Error History Changes during
operation
---
Setting
range
--- Unit of
setting
--- Default setting ---
Fault code
uU 1
· Fault display · No error stored