RS-422/485 Communications Unit Chapter 7-1
7-1-3 Names of Parts
Terminal Block
Terminating Resistance Switch
Note Set the terminating resistance switch to ON to connect the terminating
resistance.
7-1-4 Mouting Procedure
Use the following procedure to mount an RS-422/485 Communications Unit
SI-485/J7 (3G3JV-PSI485J) to a J7AZ Inverter.
1. Turn OFF the Inverter’s power supply. Mounting the RS-422/485
Communications Unit without turning OFF the Inverter’s power supply may
result in electric shock or damage to equipment.
2. Loosen the Inverter’s front cover mounting screws and remove the front
cover as shown on the left below.
3. Remove the optional cover as shown on the right below.
Terminal block
Terminating resistance switch
12345
S– S+ Shield R– R+
SW
OFF ON
A