User`s manual

97
Inverter Settings Chapter 7-2
7-2-4 Setting the Multi-function Inputs (n36 to n39)
In addition to the methods described above, the RUN command and
frequency reference can be input through RS-422A/485 communications
by setting the value 18 in any one of the parameters from n36 to n39
(multi-function input).
Subsequently, the following operations are selectable in remote mode.
None of these parameters, however, can be changed while the operation
command is being input.
When the function-set input terminal is OFF, the RUN command will be
executed according to the setting in n02 (operation command selection)
and the frequency reference will be executed according to the setting in
n03 (frequency reference selection).
When the function-set input terminal is ON, the Inverter will operate
according to the RUN command and frequency reference through RS-
422A/485 communications.
n36 Multi-function input 1 (S2) Register 0124 Hex Changes during
operation
No
Setting
range
2 to 8, 10 to 22 Unit of
setting
1 Default setting 2
n37 Multi-function input 2 (S3) Register 0125 Hex Changes during
operation
No
Setting
range
0, 2 to 8, 10 to 22 Unit of
setting
1 Default setting 5
n38 Multi-function input 3 (S4) Register 0126 Hex Changes during
operation
No
Setting
range
2 to 8, 10 to 22 Unit of
setting
1 Default setting 3
n39 Multi-function input 4 (S5) Register 0127 Hex Changes during
operation
No
Setting
range
2 to 8, 10 to 22, 34, 35 Unit of
setting
1 Default setting 6