User`s manual

103
DSR Message and Response Chapter 7-4
Response
Normal
Error
7-4-2 Data Write/Broadcast Data Write (Function Code: 10 Hex)
Settings and Response
To write data to the Inverter, such as control I/O and parameter set value
data, issue the following DSR message.
• Consecutive data of a maximum of 16 words (32 bytes for 16 registers)
can be written per DSR message.
The register number is allocated to each function item, such as control I/O
and parameter functions. The register number of each parameter is
indicated wherever the parameter is explained in this manual and in
Section 10 List of Parameters. For register numbers other than those of
parameters, refer to 7-7 Register Number Allocations in Detail.
Note 1. A parameter corresponds to one register (one word), so the “number of
registers of write data” indicates the number of parameters to be written
(i.e., the number of consecutive registers beginning with the first register
number).
2. The “number of bytes of attached data” indicates the number of bytes of
data written to the registers attached from that point onwards. The number
of registers must equal the number of bytes divided by two.
Byte No. Data Data example
(Hex)
1 Slave address 02
2 Function code 03
3 Number of bytes of attached data 08
4 Data in register No. 0020 MS B 00
5 LSB 65
6 Data in register No. 0021 MSB 00
7 LSB 00
8 Data in register No. 0022 MSB 00
9 LSB 00
10 Data in register No. 0023 MSB 01
11 LSB F4
12 CRC-16 check AF
13 82
Byte No. Data Data example
(Hex)
1 Slave address 02
2 Function code 83
3 Error code 03
4 CRC-16 check F1
5 31